Title |
A Proposal of New Hybrid Passive Harmonic Filter for AC Motor Drive Line Filter Size Reduction |
Authors |
박병주(Byung-Ju Park) ; 윤동철(Dong-Chul Yoon) ; 오정철(Jeong-Cheol Oh) ; 배병열(Byung-Yeol Bae) ; 황안일(An-il Hwang) ; 유항규(Hang-Kyu Yoo) ; 최석근(Seok-Keun Choi) |
DOI |
http://doi.org/10.5370/KIEEP.2018.67.1.001 |
Keywords |
Harmonic ; Passive filter ; THD ; AC motor drive ; Line filter |
Abstract |
ACL and DCL are have been conventionally used for reducing harmonic current on the input side of an ACMD. The current distortion ratio ITHD using ACL and DCL is only 35% to 85%, therefore to satisfy the IEEE Std. 519 requirements, the line filters has been focused as an alternative means. Those are installed between the AC power supply and the input of the ACMD, and must meet the IEEE Std. 519, be economical and be compact. To contribute to the widespread of using these line filters, we discussed concerning its topologies, simulation results, prototype test results as well as the cost evaluations. It included not only the proposed (NHHF) new hybrid harmonic filters which have both merits of simplicity and economic but also the past (BBHF) broadband harmonic filters and (HHF) hybrid harmonic filters. |