Title |
A Characteristic Study on the Power Factor Compensation Application of High Voltage Induction Motor |
Authors |
김종겸(Kim, Jong-Gyeum) ; 박영진(Park, Young-Jeen) ; 이은웅(Lee, Eun-Woong) |
Keywords |
Induction Motor ; Capacitor ; Reactor ; Power Factor ; Pump |
Abstract |
Reactor starting method has the advantage of simplicity and closed transition in spite of lower starting torque per kVA. This method allows a smooth start with almost no observable disturbance on transition and is suitable for applications such as centrifugal pumps or fans. Reactive power doesn't contribute to work but needs to sustain the electromagnetic field required for the induction motor to operate. Starting power factor of induction motor is specially lower than running power factor. Power factor application is needed to compensate for the lower power factor of induction motor. This power factor compensation systems is occasionally being hit by the effects of the starting reactor connection position at the starting, stopping of high-voltage induction motor. This paper describes voltage and current stress affected by the installation position of power factor compensation application at the reactor starting method. |