We analyzed carbonization pattern and crystal structure of polyvinyl chloride wire by thermal stress. Copper that is oxidized at normal temperature is a reddish brown. If under the thermal stress range of 500 to 700 [^{\circ}C], carbonization and exfoliation occurrence. Section structure of electric wire is same as arrangement of particle in metallograph analysis. But, as thermal stress increases, size of particle is enlarged. Electric wire displays elongation structure in SEM image analysis and elongation structure collapses when receive thermal stress at 300 [^{\circ}C]. In EDX analysis, we get the spectra of CuL, CuK, OK, and ClK. FT-IR analysis was shown new spectra with in range of 1,440{\sim}1,430\;[cm^{-1}], 1,340 [cm^{-1}], 1,240 [cm^{-1}]. |