Mobile QR Code QR CODE : The Transactions P of the Korean Institute of Electrical Engineers
The Transactions P of the Korean Institute of Electrical Engineers

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleTrans. P of KIEE
  • Indexed by
    Korea Citation Index(KCI)
Title Variation of Carbonization Pattern and Crystal Structure of Polyvinyl Chloride Wire Under the Thermal Stresses
Authors 최충석(Choi, Chung-Seog) ; 김향곤(Kim, Hyang-Kon)
Page pp.332-337
ISSN 1229-800X
Keywords Carbonization Pattern ; Crystal Structure ; Polyvinyl Chloride Wire ; Section Structure ; SEM ; EDX ; FT-IR
Abstract We analyzed carbonization pattern and crystal structure of polyvinyl chloride wire by thermal stress. Copper that is oxidized at normal temperature is a reddish brown. If under the thermal stress range of 500 to 700 [^{\circ}C], carbonization and exfoliation occurrence. Section structure of electric wire is same as arrangement of particle in metallograph analysis. But, as thermal stress increases, size of particle is enlarged. Electric wire displays elongation structure in SEM image analysis and elongation structure collapses when receive thermal stress at 300 [^{\circ}C]. In EDX analysis, we get the spectra of CuL, CuK, OK, and ClK. FT-IR analysis was shown new spectra with in range of 1,440{\sim}1,430\;[cm^{-1}], 1,340 [cm^{-1}], 1,240 [cm^{-1}].