Title |
Characteristics Analysis of Capacitor and Reactor for Harmonic Filter |
Authors |
김종겸(Kim, Jong-Gyeum) ; 박영진(Park, Young-Jeen) ; 이은웅(Lee, Eun-Woong) |
Keywords |
Harmonics ; Filter ; Non-Linear Load ; Capacitor ; Reactor |
Abstract |
Recently, application of non-linear load is gradually increased. Non-linear load produces harmonic components of current during the energy conversion transition. Passive filter is used for reducing of harmonics in the user power systems. This filter, which is composed of capacitor and reactor, frequently get out of order by electrical stress. There are voltage and current increase when capacitor and reactor are applied in the user's filter systems. If increased voltage and current is above stipulated values, they have severely an influences on the life of capacitor and reactor. This paper describes that the voltage and current of capacitor used for filter is within the limits of allowable values, but reactor is beyond the limits and reveals spike voltage. Therefore this phenomenon brings about premature fault of reactor and capacitor. |