Title Performance Analysis for Passive Filter Considering Allowable Limits of Tolerance
Authors 김종겸(Kim, Jong-Gyeum) ; 김일증(Kim, Il-Jung)
Page pp.38-43
ISSN 1229-800X
Keywords Non-linear load ; Harmonics ; Reactor ; Capacitor ; Resonance ; Voltage-Stress
Abstract Reactors are connected with capacitors to passive filter circuits for reducing harmonics caused by power conversion application. This passive filter frequently gets out of order by voltage and current stress. Especially filter reactor has too much voltage harmonics components, its trouble rate is higher than capacitor. In this paper, we analyzed voltage and current of reactor and capacitor used for passive filter by simulation and measurement. If reactor has a tolerance on variation of reactance value, series resonance frequency is different from originally filter design frequency and parallel resonance can be generated at the close point of the former. Because filter absorbs harmonic component of non-linear load, much of harmonic voltage has been impacted on reactor.