Title Effect on Vibration According to the Load Capability and Elapsed Year of Power Transformer(154kV) in Operation
Authors 김영달(Kim, Young-Dal) ; 김성중(Kim, Sung-Joong)
Page pp.172-177
ISSN 1229-800X
Keywords Transformer ; Vibration ; Correlation Coefficient ; Regression Analysis ; Load Capability ; Elapsed Year
Abstract Most of the causes of the failures of power transformers in operations are mechanical defects due to vibration. To identify these causes, the vibration phenomenon was measured from the power transformers in operation in the substations under the Daejeon power transmission district office of KEPCO. The measurement was performed in a 6{times}4 structure on one side of the transformer. The vibration of the measured points was presented in 2D and 3D, and analyzed. The results according to the period in use of the transformer and the load applied to the transformer were analyzed. These results will be used as basic data to establish the vibration standard for the power transformer, In addition, with a load capability and vibration phenomenon correlation and regression analysis to identify by way of function was reached. And the vibration phenomenon pass a years with changes and to analyze correlation, was estimated to bring in the function. And then through the analysis of power transformers to set standards based on vibration data was used to.