Title A Study on Condenser Characteristics at the Series Connection of Condenser and Reactor Under Voltage Unbalance
Authors 김일중(Kim, Il-Jung) ; 김종겸(Kim, Jong-Gyeum) ; 박영진(Park, Young-Jeen) ; 김성헌(Kim, Sung-Hun)
Page pp.325-329
ISSN 1229-800X
Keywords Voltage Unbalance ; Condenser ; Reactor ; Voltage Rise ; Stress
Abstract Capacitor has been used principally for the power factor compensation long ago. However now it does as passive filter to reduce harmonics of nonlinear load with reactor. Most of the customer's low-voltage feeder has been designed with approximately balanced and connected at the 3 phase four wire system. But voltage and current unbalance is appeared by the mixing operation of single or three phase load etc. The addition of reactor at the condenser may rise its terminal voltage. Voltage and current values above rating can act on electrical stress on the condenser. In this paper, we calculated and measured that voltage, current and capacity of condenser are changed under the voltage balance. We conclude that magnitude and deviation of phase voltage act on major point of electrical stress.