Title A Development of Ethernet-Based Remote Diagnosis System for DC Voltage Smoothing Capacitor using DSP
Authors 손진근(Shon, Jin-Geun)
DOI https://doi.org/10.5370/KIEEP.2011.60.2.094
Page pp.94-98
ISSN 1229-800X
Keywords Equivalent Series Resistance(ESR) ; Ethernet-Based Remote Diagnosis System ; DC Link Electrolytic Capacitor ; Power Electronic System ; Ripple Power Losses
Abstract Electrolytic power capacitors today form essential components for virtually any power electronic system such as DC/DC converter or UPS. Frequently, electrolytic capacitors for DC link voltage smoothing are the key components which determine the life cycle of the whole unit and often are responsible for converter breakdown failures. In this paper, ethernet-based remote diagnosis system for DC voltage smoothing capacitor using DSP control board is developed. To estimate the status of the capacitor, the equivalent series resistor(ESR) of the component has to be determined. The ESR detection scheme is based on the determination of the capacitor ripple power losses calculated from DC link voltage/current measurement. Experimental results show the veridity and reliability of the proposed ethernet-based remote on-line capacitor diagnosis system.