Title Fault Locator using GPS Time-synchronized Phasor for Transmission Line
Authors 이경민(Lee, Kyung-Min) ; 박철원(Park, Chul-Won)
DOI https://doi.org/10.5370/KIEEP.2016.65.1.047
Page pp.47-52
ISSN 1229-800X
Keywords COMTRADE format ; Fault location scheme ; GPS time synchronized ; IED ; Impedance measurement ; Service restoration ; Transmission line fault ; Two-end terminals
Abstract Fault location identification in the transmission line is an essential part of quick service restoration for maintaining a stable in power system. The application of digital schemes to protection IEDs has led to the development of digital fault locators. Normally, the impedance measurement had been used to for the location detection of transmission line faults. It is well known that the most accurate fault location scheme uses two-ended measurements. This paper deals with the complete design of a fault locator using GPS time-synchronized phasor for transmission line fault detection. The fault location algorithm uses the transmitted relaying signals from the two-ended terminal. The fault locator hardware consists of a Main Processor Unit, Analog Digital Processor Unit, Signal Interface Unit, and Power module. In this paper, sample real-time test cases using COMTRADE format of Omicron apparatus are included. We can see that the implemented fault locator identified all the test faults.