Title |
Development and Demonstration of Trial-run Automation System of Energy Storage System for Frequency Regulation |
Authors |
임건표(Lim, Geon-Pyo) ; 최요한(Choi, Yo-Han) ; 이승민(Lee, Seung-Min) ; 박찬욱(Park, Chan-Wook) |
DOI |
https://doi.org/10.5370/KIEEP.2017.66.3.110 |
Keywords |
Trial-run automation system ; Energy storage system ; Frequency regulation ; Power system |
Abstract |
System to automate the trial-run of energy storage system for frequency regulation was developed and demonstrated. Basic strategy was developed on the basis of trial-run procedure and verified in the computer simulation tool. The algorithm was developed and coded for 4MW trial-run automation system. 4MW trial-run automation system was connected to 4MW energy storage system for frequency regulation in Jocheon substation of Jeju city and demonstrated. 24MW trial-run automation system was developed on the basis of 4MW trial-run automation system and verified by operation system for 24MW energy storage system for frequency regulation. The operation system has own simulation model of energy storage system and power system. The verification was performed to improve the system in the view of user. 24MW trial-run automation system was demonstrated in 32MW Ul-san and 36MW Non-gong energy storage system. All tests of trial-run was done by manual and first they ware taken 1 week with no trial-run automation system. The manual trial-run tests were taken by maximum three times. Trial-run test by trial-run automation system was taken 2 days. The system helps reduce the trial-run test period and improve the accuracy of tests. |