Mobile QR Code QR CODE : The Transactions P of the Korean Institute of Electrical Engineers
The Transactions P of the Korean Institute of Electrical Engineers

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleTrans. P of KIEE
  • Indexed by
    Korea Citation Index(KCI)
Title Selection of Phase Synchronization Method to Improve Power System Connection Phase Tracking Performance of Hybrid Active Power Filter
Authors 박현수(Hyun-soo Park) ; 이현재(Hyun-jae Lee) ; 박훈양(Hoon-yang Park) ; 손진근(Jin-geun Shon)
DOI https://doi.org/10.5370/KIEEP.2021.70.3.133
Page pp.133-138
ISSN 1229-800X
Keywords DSOGI-PLL; DSOGI-FLL; Hybrid Active Power Filter; Positive Sequence; Second Order Generalized Integrator
Abstract In this paper, to improve power system connection phase tracking performance of the hybrid active power filter, compared and analyzed the robust phase synchronization method even in power sources including disturbances such as frequency and phase angle variance. Among the SOGI-based methods used to obtain a stable input voltage, the DSOGI-PLL method that tracks the phase angle of the input voltage and the DSOGI-FLL method that tracks the frequency of the system are applied to the hybrid active power filter to compare and analyzed. As a result, the phase synchronization characteristics of DSOGI-FLL method is more robust than the DSOGI-PLL method, and the current compensation characteristics is also more accurate and faster. Therefore, it is judged that the DSOGI-FLL method needs to be selected to improve the power system phase tracking performance of the hybrid active power filter.