The Characteristics of a Bypass Air Conditioning System for Load Variation |
Keywords |
Apparatus dew point ; 장치노점온도 ; Bypass control ; 바이패스제어 ; GSHF ; 총현열비 ; ESHF ; 유효현열비 ; RSHF ; 실현열비 ; Part load ; 부분부하 |
Abstract |
Bypass air conditioning systems are divided into three types; an outdoor air bypass, a mixed air bypass and a return air bypass system. What makes the return air bypass system more effective is that it directs all of moist outdoor air through the cooling coil. The bypass air conditioning system can maintain indoor R.H (Relative Humidity) less than a conventional CAV (Constant Air Volume) air conditioning system by adjusting face and bypass dampers at part load. When a design sensible load (the ratio of sensible load to total sensible load) is 70 percent (at this time, RSHF (Room Sensible Heat Factor):0.7), indoor R.H was maintained 59 percent by the return air bypass system, but 65 percent by the conventional CAV air conditioning system (valve control system). The bypass air conditioning system can also improve IAQ (Indoor Air Quality) in many buildings where the number of air change is high. |