Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title An Experimental Study on the Measurement Error in the Performance Testing of Air Conditioners Using a Psychrometric Calorimeter
Authors 김봉훈
Page pp.415-423
ISSN 12296422
Keywords Psychrometric calorimeter ; 건습구식 칼로리미터 ; Air conditioner ; 공기조화기 ; Measurement error ; 측정오차 ; Calibration ; 교정 ; Cooling capacity ; 냉방능력
Abstract An experimental study using a psychrometric calorimeter was conducted to investigate the temperature and pressure measurement errors permitted for determining cooling capacity of an air conditioner. First, the instrument calibration was made in accordance with the related test methods and guidelines in order to accurately evaluate basic performance (cooling capacity and air flow rate). Secondly, a parametric study was performed to examine the effect of measurement error involved in temperature and pressure measuring instruments on the cooling capacity calculation.
From the results, it was found that the degree of accuracy for both temperature and pressure measurements played an important role on the error occurring in the determination of cooling capacity and needed to be maintained within a certain value to guarantee required accuracy of cooling capacity.