Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title A Study on the Heat Transport Limitations of a PFC(FC-72) Two-Phase Closed Thermosyphon for Cooling Power Semiconductors
Authors 박용주 ; 홍성은 ; 김철주
Page pp.725-733
ISSN 12296422
Keywords Two-phase closed thermosyphon ; 밀폐형 2-상 열사이폰 ; Limitation ; 한계 ; Fill charge ratio ; 충전율 ; Tilt angle ; 경사각 ; Dry-out ; 드라이-아웃 ; Flooding ; 플러딩
Abstract In this study, the heat transport limitations of a two-phase closed thermosyphon were investigated. For the test, a two-phase closed thermosyphon(: 600mm,: 105 mm,: 75mm,: 420mm,: 22.2mm, container: copper(inner grooved surface), working fluid: PFC(C6F14)) was fabricated with a reservoir that can change the fill charge ratio. The following was imposed as the factors on the heat transport limitations of a two-phase closed thermosyphon.
1) Fill charge ratio of the working fluid.
2) Tilt angle of the longitudinal axis.
From the experimental data, some results were obtained as follows. When the fill charge ratio was relatively small(Ψ<20%), the heat transport limitation occurred about 100W by dry-out limitation. However over 40%, it showed nearly constant value(500W) by flooding limitation. The heat transport limitation according to the tilt angle increased smoothly until the tilt angle was 60°, after then decreased slowly.