Title |
Analysis on Thermal Environment in the Rotunda of New National Museum of Korea |
Authors |
이승철 ; 조영진 ; 김두성 ; 이재헌 ; 김홍범 |
Keywords |
Thermal comfort ; 온열쾌적도 ; Predicted mean vote ; PMV, 예상온열감 ; Predicted percentage of cissatisfied ; PPD, 예상불만족률 ; Thermal stratification ; 열성층화 ; Glass sidewall ; 유리측벽 |
Abstract |
Thermal comfort in the Rotunda which is high wide visiting space of the new national museum of Korea has been numerically investigated in this paper. To evaluate thermal comfort of the Rotunda, well-known indices, PMV and PPD were introduced. The results of present investigation show that thermal comfort is satisfied at the breathing zone of the visiting space. However a thermal stratification with 9℃ of temperature difference occurs along the height of the Rotunda which makes the thermal environment worse. For example, the PPD value reaches up to 50% in the 6th floor connection passage. Consequently, additional HVAC design factors should be considered in order to reduce the large thermal stratification. |