Title |
A Study on the Dehumidification Control to Prevent Condensation for Radiant Floor Cooling |
Keywords |
Radiant floor cooling ; 바닥복사냉방 ; Dehumidification system ; 제습시스템 ; Ondol ; 온돌 ; Condensation ; 결로 ; Control ; 제어 |
Abstract |
In the forming of an integrated system of radiant floor cooling and dehumidifying, chilled coil can be used for cooling and dehumidification. Therefore, it is necessary to find the efficient control method which can eliminates latent load efficiently. This study has been conducted to find this method by dividing the dehumidification system into 3 types according to the control variables and analyzing characteristics of each system. To prevent the floor surface condensation, the amount of condensation can be manipulated by water temperatures, water flow rates in chilled coil, and air flow rates passing by it. So dehumidification system control can be divided into constant air flow control and variable air flow control. Regarding dehumidification control, variable air flow control, which eliminates latent load rather than sensible load, is preferable to constant flow control. |