Title |
A Preliminary Study on the In-line Concentration Measurement of Absorbent Solution |
Keywords |
In-line measurement ; in-line 측정법 ; Concentration ; 농도 ; Absorption fluid ; 흡수용액 ; Density ; 밀도 ; Buoyancy ; 부력 |
Abstract |
Titration method is one of the widely used methods for the concentration measurement of absorbent ammonia/water. However, this method is inconvenient because the solution should be extracted for the measurement. Moreover, significant error can be introduced by the evaporation of ammonia during the sampling and measuring procedure. In this study a reliable in-line concentration measurement method was proposed. To prove the validity of the concept, a measuring apparatus was designed, built, and tested with water. It is found that the location of flow inlet and exit is important in the measurement accuracy. The flow inlet and exit located in the middle of the test cell showed the best result. By the error analysis, it is expected that the ammonia concentration can be measured within the error of ±0.18% assuming the error of 0.1K in temperature measurement and 0.1g in weight measurement. |