Title |
Numerical Analysis of Thermal Environments and Comfort for Local Air Conditioning System |
Keywords |
Numerical simulation ; 수치모사 ; Local air conditioning system ; 국부공조시스템 ; PMV ; 예상온열감 ; Computational fluid dynamics ; 전산유체역학 |
Abstract |
Numerical simulation using computational fluid dynamics(CFD) is performed to calculate the velocities and temperature profiles of air in adjacent to a worker within the individual local air conditioning system. The calculation domain is the space of ㄴ between walls and a worker in the climate room. The fresh air is supplied from the three different inlets located on the right, left and center wall in the climate room. In this study, the calculated data of velocities and temperature profiles of air in the nearest the skin of a worker are used to calculate the PMV(Predicted Mean Vote) for evaluation of thermal comfort of a worker in the local air conditioning system. Because the data of velocities temperature profiles of air in adjacent to a worker and the PMV of a worker are the design parameters of the local air conditioning system. The results of calculation show that the fresh air velocity and injection position are closely related to the PMV value. In individual air condition system of ㄴ, the appropriate PMV are obtained when the fresh air velocity and position are 1.0m/s, throat of a worker and are 1.5m/s, head of a worker, respectively. The method of numerical calculation is effective to obtain the optimum velocity and position of the fresh air for optimum the PMV and energy saving in individual local air conditioning system. |