Performance Evaluation of Heat Exchangers due to Air-side Particulate Fouling in the Air Conditioners |
Authors |
안영철 ; 조재민 ; 이재근 ; 이현욱 ; 안승표 ; 윤덕현 ; 하삼철 ; 강태욱 |
Keywords |
Heat exchanger ; 열교환기 ; Particulate fouling ; 입자상 파울링 ; Pressure drop ; 압력손실 ; Cooling capacity ; 냉방능력 ; Air conditioner ; 에어컨 |
Abstract |
The air-side particulate fouling in the heat exchangers of HVAC applications degrades the performance of cooling capacity, pressure drop across a heat exchanger, and indoor air quality. Indoor and outdoor air contaminants foul heat exchangers. The purpose of this study is to investigate the cooling performance and pressure drop on the air-side particulate fouling of heat exchangers for air conditioners. Air conditioners being used in the field such as inn, restaurant, and office are collected in chronological used order. Test results show 15% decrease of the cooling capacity and 44% increase of the pressure drop for the 7 years air conditioners used in the seaside inn. |