Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Analysis of the Condenser Performance Installed in the Air-Conditioning Plant Room of a High-Rise Building
Authors 최석호 ; 이관수 ; 김병순
Page pp.586-594
ISSN 12296422
Keywords Condenser ; 응축기 ; Air-conditioning plant room ; 실외기실 ; Draft ; 외풍 ; COP ; 성적 계수 ; Arrangement of condenser ; 응축기 배치 ; High-rise building ; 고층 건물
Abstract The performance of the condenser installed in the air-conditioning plant room of a high-rise building was studied numerically. The effect of the draft direction on the performance of an air-conditioner was analyzed. The on-coil temperature of the condenser was investigated by varying the arrangement and location of the condenser in the air-conditioning plant room. The performance of an air-conditioner was also evaluated by using COP(coefficient of performance) and CGPI(condenser group performance indicator). The condenser in an air-conditioning plant room should be arranged in such a manner that the fan of the condenser is facing the outside of the building to exhaust the hot air directly. The model by which the condenser is located at the lower-left end of an air-conditioning plant room can prevent the hot air from reentering, and allow indrafting of fresh air. When the direction of draft is to the frontal face of the building, the performance of the condenser above 30th floor is degraded.