Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title A Generalized Empirical Correlation on the Mass Flow Rate through Adiabatic Capillary Tubes with Alternative Refrigerants
Authors 최종민 ; 장용희 ; 김용찬
Page pp.744-750
ISSN 12296422
Keywords Capillary tube ; 모세관 ; Generalized correlation ; 일반화된 상관식 ; Mass flow rate ; 유량 ; Refrigerator ; 냉장고 ; Heat pump ; 열펌프
Abstract The performance of adiabatic capillary tubes are measured to provide the database for a generalized correlation. Test conditions and capillary tube geometries are selected to cover a wide range typically observed in air-conditioning and heat pump applications. Based on extensive experimental data for R22, R290, and R407C measured in this study, a generalized correlation for refrigerant flow rate in adiabatic capillary tubes is developed by implementing dimensionless parameters for tube inlet conditions, capillary tube geometry, and refrigerant properties. The correlation yields good agreement with the present data for R22, R290, and R407C with average and standard deviations of 0.9% and 5.0%, respectively. In addition, approximately 97% of the data for R12, R134a, R152a, R410A, and R600a obtained in the open literature are correlated within a relative deviation of ±15%.