Title Part-Load Performance Test of a Screw Chiller with Economizer using R22 and R407C
Authors 장영수 ; 이용철 ; 김영일
Page pp.902-909
ISSN 12296422
Keywords Screw chiller ; 스크류 냉동기 ; Part-load ; 부분부하 ; Economizer ; 이코노마이저 ; R22, R407C
Abstract Screw compressor type chillers are widely used in refrigeration for capacity over 30RT. In general, chillers operate under part-load conditions. Therefore, information on characteristics at part-load is very important in view of chiller performance and energy economy. In this study, performance tests of part-load and economizer system using R22 and R407C have been performed for various secondary fluid temperatures. Adoption of an economizer system increased the cooling capacity and improved COP except for lower part-load condition when injection volume ratio is 1.01. For the same cooling capacity condition at part- load, COP of both non-economizer and economizer system showed similar values.