Title |
A Study on the Thermal Characteristics of a MgO/H2O Chemical Heat Pump |
Authors |
권오경 ; 윤재호 ; 김정욱 ; 이진호 ; 加藤之貴 |
Keywords |
Heat pump ; 히트펌프 ; Dehydration ; 탈수 ; Hydration ; 수화 ; Magnesium oxide ; 산화 마그네슘 ; Heat storage ; 축열 ; Heat output ; 열출력 ; Co-generation ; 열병합발전 |
Abstract |
The chemical heat pump based on the Dehydration/Hydration process with a MgO/H2O system has been researched. The reactor bed could be expected to store the heat around 200~370℃ by the dehydration reaction and to release the heat around 100~160℃ by the hydration reaction under the heat amplification mode operation. The heat output rate of the heat pump system was evaluated using the experimentally determined parameters. The results show that 6~50W/kg of heat output and 0.5~0.8 of heat recovery ratio are attainable. The heat pump will be applicable for a load leveling in a co-generation system by chemical storage of surplus heat at low heat demand and by supplying heat in the peak load period. |