Title |
Experimental Study on Cooling Characteristics of Multi-Air Conditioner using Inverter Scroll Compressor |
Authors |
권영철 ; 고국원 ; 진의선 ; 허삼행 ; 전용호 ; 이영덕 ; 박인규 |
Keywords |
Multi-A/C ; 멀티 에어컨 ; Inverter ; 인버터 ; Cooling capacity ; 냉방능력 ; COP ; 성능계수 ; Part load ; 부분부하 ; Scroll compressor ; 스크롤 압축기 |
Abstract |
In the present study, the cooling characteristics of the multi-air conditioner (A/C) using an inverter scroll compressor are experimentally investigated for the number of the indoor units and the operating conditions(20℃, 24℃, 26℃) under the cooling standard conditions by KS C 9306. In the case of the simultaneous operation for 3 indoor units, the cooling capacity, the mass flow rate and the input power have a decreasing trend and COP has an increasing trend, with decreasing the difference in the operating temperature of the indoor unit and the room temperature. In the case of the simultaneous operation for 2 indoor units, the COP of the indoor unit with large cooling capacity is high when the operating temperature is high, but the COP of the indoor unit with low cooling capacity is high when the operating temperature is low. In the case of the single operation for one unit, when the large cooling capacity of the indoor unit is less than 50% the compressor operates at the minimum operation frequency region and the COP decreases. |