Title |
Measurement of Heat Transfer Coefficient in a Flooded Evaporator through Wilson Plot Method |
Keywords |
Wilson Plot ; 윌슨플롯 ; Heat transfer ; 열전달 ; R134a, R123, Flooded evaporator ; 만액식 증발기 ; Enhanced tube ; 전열촉진관 |
Abstract |
Heat transfer coefficients of enhanced tubes in a flooded evaporator are measured through Wilson Plot method. And the correlations are proposed to design a flooded evaporators. Overall heat transfer coefficients are composed of the heat transfer coefficients both inside and outside tubes. Usually the experiments have been conducted separately. But there have been many difficulties like setting up the equipments and measuring the wall temperature. Wilson Plot method makes it possible to measure the separated transfer coefficients at the same equipment through experimental skills. So the cost and time can be reduced. And the results are reliable enough to use for design. Heat transfer coefficients inside the tube were able to be correlated uniquely in spite of various outside conditions. Boiling heat transfer of R134a is more dependent on the saturation temperature and much higher than that of R123. |