Title |
ADPI Characteristics of Line Diffuser in a Room with Perimetric Heating Load |
Keywords |
ADPI ; 공기확산성능지수 ; Throw distance ; 도달거리 ; Characteristic length ; 대표길이 ; Heat load ratio ; 부하비 ; EDT ; 유효드래프트온도 ; T/L ratio ; T/L비 |
Abstract |
It is difficult to apply a conventional selection guide for diffusers when the diffuser is installed in a perimeter zone, because the air diffusion performance index(ADPI) vs. throw/length(T/L) ratio curve listed in conventional guide does not consider the perimetric heating load through the walls. The objective of this study is to evaluate the effect of the perimetric heating load on the ADPI and propose a selection guide for a proper line diffuser when perimetric heating load exists. The velocity and temperature distributions and the ADPI values are obtained numerically with various heat load ratios and air flow rates. The velocity and temperature distributions and the ADPI values are analyzed by CFD in case of various heat load ratios and air flow rates. Also, ADPI was calculated by those results. The ADPI values by numerical results are compared with an existing experimental data to verify the method for the evaluation of ADPI proposed in a present study. In case of a line diffuser installed at the high side wall, the ADPI decreases according to the increases of the flow rate on every heat load ratio of the present study except 0.75. The ADPI vs. T/L ratio curves have been proposed for the heat load ratios of 0.25, 0.5, 0.75 to guarantee the comport thermal environment when diffusers are installed in perimeter zone. |