Title |
Evaluation of Energy Consumption of HVAC System for Air Filter Pressure Difference Change in Commercial Buildings |
Keywords |
공기조화기 ; 공기필터 ; 에너지 성능 ; 동적 시뮬레이션 ; HVACSIM+ AHU ; Air filter ; Building energy performance ; Dynamic simulation ; HVACSIM+ |
Abstract |
Air handling unit(AHU)'s air filter pressure difference is important for energy consumption and indoor air quality. Both energy performance data and air filter differential pressure of AHU in real office buildings were monitored and analyzed to investigate quantitatively energy impact as dust buildup level on air filter grows. We also modeled and simulated CAV system using HVACSIM+ program to examine the energy effect of dust buildup on filters. Through analysis of time series pressure drop data, the filter pressure difference rate has been increased due to cumulative supply air flow rate increase. As filter pressure drop increased to 1 inch water column, it is found that the supply air flow rate was decreased by 10%, the chilled water flow rate was increased by 5.9% and the pump energy consumption was increased to 5.9%. |