Title |
Analysis of Heating Energy in a Korean-Style Apartment Building 3:The Effect of Room Condition Settings |
Keywords |
난방에너지 ; TRNSYS ; 동적 열부하계산 ; 존별 제어 ; 환기 ; 설정온도 Heating energy ; TRNSYS ; Dynamic load calculation ; Zone control ; Ventilation ; Set temperature |
Abstract |
The present paper deals with heating energy estimation in Korean-style apartments, paying special attention to the effect of room condition settings. Two types of heating modes are considered: continuous single-zone and scheduled multi-zone. In the latter, zones during unoccupied periods remain unconditioned. Also analyzed are sensitivities in heating energy with respect to the air change rate and the set temperature. The energy use is estimated with TRNSYS 15, a dynamic load calculation program. Heating energy for the actual residential condition(1.0ACH and 24℃) appears to be nearly the same as that for a typical design standard(1.5ACH and 20℃). The air change rate affects heating energy as sensitively as the set temperature. For all the simulated cases, the scheduled multi-zone heating mode is more energy-efficient than the continuous single-zone. Heating energy depends appreciably on the shading factor. It is expected that considerable heating energy for apartment houses can be saved by employing a multi-zone mode along with appropriate control devices. |