Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title Study on the Performance Optimization of Commercial Metal Hydride Refrigerator Powered by Exhaust Gas from Micro Gas Turbine
Authors 김형식 ; 손화승 ; 최경식
Page pp.824-829
ISSN 12296422
Keywords Metal hydride refrigerator ; 수소흡장냉동기 ; Micro gas turbine ; 마이크로가스터빈 ; Optimum operating condition ; 최적작동조건 ; Cooling capacity ; 냉동능력
Abstract MHR(Metal Hydride Refrigerator) powered by MGT exhaust gas is investigated to find out the optimum conditions corresponding to MGT operating powers. There are many factors to affect cooling capacity of MHR. In this study, the effect of switching time, flow rate of brine on cooling temperature and capacity is investigated. The present results show (1) hydrogen reaction is saturated with 25min switching time at 25kW MGT power, (2) cooling power shows maximum phenomenon with increasing switching time, (3) optimum switching times are 20 minutes for 15kW MGT power and 15 minutes for 20, 25kW MGT power, (4)according to increasing brine flow rate, cooling capacity shows decrease at 15kW MGT power and changes little at above 20kW MGT power.