Title Evaluation of Thermal Performance for Air-Barrier Air-conditioning System in Perimeter Zone by Scale Model Experiment and Simulation
Authors 함흥돈 ; 박병윤 ; 손장열
Page pp.947-955
ISSN 12296422
Keywords 열성능 ; 공기막 공조방식 ; 기존 공조방식 ; 수치해석 Thermal performance ; Air-barrier air-conditioning system ; Conventional air-conditioning system ; Simulation
Abstract For the purpose of evaluating the thermal performance for air-barrier air conditioning system in perimeter zone, two air-conditioning systems, conventional perimeter air- conditioning system and air-barrier system, are evaluated and compared by scale model experiment and simulation during cooling season. As a result, measurement shows that supply air velocity of 1m/s in the upstream direction at perimeter is more effective. Air-barrier system could reduce the cooling energy by 10∼20% compared with conventional system. Numerical simulation was carried out considering solar effect for reliable result. This method has improved the accuracy of numerical simulation for the space affected by the solar radiation. Both measurement and simulation results show that supply air velocity of 1m/s at perimeter is the most effective.