Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title A Study on the Factors Affecting the Performance of Paper Heat Exchanger for Exhaust Heat Recovery
Authors 정민호 ; 유성연
Page pp.956-964
ISSN 12296422
Keywords Paper heat exchanger ; 종이 열교환기 ; Plate heat exchanger ; 판형 열교환기 ; Heat transfer ; 열전달 ; Pressure drop ; 압력손실 ; Heat recovery ; 열회수
Abstract In order to control indoor air quality and save energy, it is needed to install a suitable ventilation system equipped with heat exchanger for heat recovery. The purpose of this research is to find the factors affecting the performance of paper heat exchanger for exhaust heat recovery, which can be applied directly to the conventional ventilation unit, air- purifier, and air-conditioning system. In this study, thermal performance and pressure loss of the paper heat exchanger are measured and compared at various operating conditions. The effectiveness of sensible, latent and total heat at the face velocity of 0.75m/s are 77%, 47% and 57% in the cooling condition and 77%, 59% and 69% in the heating condition, respectively. The effectiveness for sensible heat is only affected by velocity. On the other hand, the effectiveness for latent heat is affected by temperature and relative humidity.