Title |
A Study on the Optimal Orifice Location for Air flow Measurementin an Air Duct Leakage Tester |
Keywords |
Optimal location ; 최적위치 ; Flow measurement ; 풍량측정 ; Orifice ; 오리피스 ; Air duct leakage tester ; 덕트누기시험기 |
Abstract |
In this study, five experiments were carried out, with an orifice located down-stream of a fan in case I where upstream duct length is 6D, and that in the downstream is 4D and different downstream distance to the fan in the rest, so as to determine the optimal location of the orifice and reduce the duct length of airflow measurement device. The re-sulting flow rate-pressure drop correlations were found to satisfy the limitation of SMACNA standard, which specified an error of ±7.5% based on the real flow rate. Also, the best one of five cases was achieved with the orifice located midway of the orifice duct four times its diameter long |