Title |
A Study on Improvement of Performance for PerforatedType Total HEX Element |
Authors |
곽경민(Kyung-Min Kwak) ; 배철호(Cheol-Ho Bai) ; 김지용(Jee-Yong Kim) ; 주의성(Euy-Sung Chu) |
Keywords |
폐열회수형 환기장치 ; 다공형 ; 전열교환기 소자 ; 온도효율 ; 습도효율 ; 전열효율 Heat recovery ventilation system ; Perforated type ; Element ; Temperature efficiency ; Latent efficiency ; Enthalpy efficiency ; |
Abstract |
The perforated type element for a heat recovery ventilation system has been studied to improve the performance. Four holes of diameter of 6mm are punched out for each flow channel to break the boundary layer development and increase the turbulence. KS cooling and heating conditions and test procedures are applied for study. The efficiencies are compared to those of the typical element with smooth surface. For cooling operations, the temperature, latent and enthalpy efficiencies increase 2.5%, 18% and 8%, respectively. For heating operations, the temperature, latent and enthalpy efficiencies increase 3%, 5% and 3.2%, respectively. |