Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title A Real Time Measurement of Ice Concentration of Ice Slurry in Pipe
Authors 정해원(Hae-Won Jung) ; 백종현(Jong-Hyeon Peck) ; 김용찬(Yongchan Kim) ; 강채동(Chaedong Kang) ; 홍희기(Hiki Hong)
Page pp.599-606
ISSN 1229-6422
Keywords 굴절률 ; 아이스슬러리 ; 동결점 ; 농도 ; 밀도 ; 빙충전율 ; 얼음분율 Refractive index ; Ice slurry ; Freezing point ; Concentration ; Density ; IPF ; Ice concetration
Abstract An experimental study was performed to measure a ice concentration of ice slurry flowing in a pipe in a real time. In the present paper, we suggested a measuring method by a refractive index and compared it to other methods by a freezing point and a density. To measure the refractive index of the solution, ice particles in the ice slurry should be completely removed and a hydro-cyclone was introduced instead of a mesh. The measuring method through the refractive index coincided with the density method using the real-time solution density within ±5% error range, having the error range less than the other two methods. In the other hand, the measuring method through the density has a good resolution, but the result using the initial density of the solution was different more than 10% error from that using the real-time density. And it has an error range 1.5 times greater than the method through the refractive index.