Analysis of Office Building HVAC System Drawings |
Authors |
박종일(Jong-Il Park) ; 김세환(Se-Hwan Kim) ; 김동규(Dong-Kyu Kim) |
Keywords |
부하계산 ; 공조설비 설계 ; 사무용 건축물 ; 유효 면적비 Load calculation ; HVAC design ; Office building ; Rate of effective area |
Abstract |
Optimized capacity of equipments are essential for energy saving and low cost construction and operation. So we must use proper design data for HVAC system design. We investigated for architectural data, equipment capacity, cooling and heating load design criteria of 52 office buildings. Following research results were obtained by carrying out each task. Office building effective area rate is 63%. The average building cooling load of South Korea is 140W/㎡ and average heating loads in Seoul and Pusan area are 120∼130W/㎡ and 70∼80W/㎡. We also analysised HVAC design criteria. Person ratio in effective building area is 0.2 person/㎡, sensitive and latent heat loads of a person are 60W and 65W, light and equipment loads of office buildings are 25W/㎡ and 20W/㎡. |