Title |
Energy Performance Evaluation of a New Commercial Building using Calibrated As-built Simulation with Monitoring Data |
Keywords |
신축건물 ; 에너지절약 설계요소 ; 보정된 시뮬레이션 ; 성능평가 New building ; Energy conservation design measure ; Calibrated as-built simulation ; Performance evaluation |
Abstract |
The performance evaluation of a new building is becoming more important because efficient design alone is often not sufficient to deliver an efficient building. However, there is a lack of standard evaluation methods to measure the energy performance of a new construction that has Energy Conservation Design Measures (ECDMs). This study presents an enhanced method based on calibrated whole-building simulation for evaluating the energy performance of new commercial buildings and demonstrates its use using a case-study building, including:an Energy Use Index (EUI) comparison with sub-metered data and an evaluation of the performance of specific ECDMs. The use of this method has determined that the case-study building was shown to use approximately 47% less energy than the base-case building that has the same shape and function as the case-study building (i.e., calibrated as-built simulation model), but doesn’t include the simulated ECDMs. |