Title |
Study on the Counterflow Regenerative Evaporative Cooler with Finned Channels |
Authors |
최봉수(Bong Su Choi) ; 홍희기(Hiki Hong) ; 이대영(Dae-Young Lee) |
Keywords |
재생증발식 냉방기 ; 증발 냉각 ; 주름판 ; 핀삽입 채널 Regenerative evaporative cooler(REC) ; Evaporative cooling ; Corrugated plate ; Finned channel |
Abstract |
The regenerative evaporative cooler(REC) is to cool a stream of air using evaporative cooling effect without an increase in the humidity ratio. In the regenerative evaporative cooler, the air can be cooled down to a temperature lower than its inlet wet-bulb temperature. Besides the cooling performance, for practical application of the regenerative evaporative cooler, the compactness of the system is also a very important factor to be considered. In this respect, three different configurations, i.e., the flat plate type, the corrugated plate type, and the finned channel type are investigated and compared for the most compact configuration. The optimal structure of each configuration is obtained individually to minimize the volume for a given effectiveness within a limit of the pressure drop. Comparing the three optimal structures, the finned channel type is found to give the most compact structure among the considered configurations. The volume of the regenerative cooler can be reduced to 1/8 by adopting the finned channel type as compared to that of the flat plate type. |