Title |
An Analysis of the Optimal Thermal Storage Time of Air-Conditioning System with Slab Thermal Storage : An Analysis by the Gradient Method Algorithm |
Keywords |
슬래브 축열 ; 최적축열시간 ; 구배법 알고리즘 ; 케이스스터디 Slab thermal storage ; Optimal thermal storage time ; Gradient method algorithm ; Case study |
Abstract |
In this paper, the optimal thermal storage time of an air-conditioning system with slab thermal storage in office building was analyzed on the basis of the gradient method algorithm. The sum of room temperature deviation and heat extraction rate was set to the criterion function. It was calculated that four hours is the optimal thermal storage time under the standard evaluation criterion. Furthermore, some case studies were executed by controlling ratio of weight functions of room temperature deviation and heat extraction rate in criterion function. It is possible to design many kinds of optimal operation of an air-conditioning system with slab thermal storage by controlling ratio of the weight functions in criterion function. |