Title |
A Study on the Decrease of Compressor Discharge Temperature Using Subcooling Bypass Technology |
Authors |
곽경민(Kyungmin Kwak) ; 배철호(Cheolho Bai) |
Keywords |
SBT ; 토출온도 ; 에너지 효율 ; bypass 율 Subcooling bypass techonology ; Discharge Temperature ; EER ; Bypass rate |
Abstract |
The purpose of the study is to decrease the refrigerant temperature at the outlet of the compressor under high thermal load conditions for air cooled vapor compression refrigeration system. The subcooling bypass line called subcooling bypass technology(SBT) is installed to the window type A/C system to investigate the performance test. The standard air calorimeter test method is applied to measure the refrigerant temperature at the outlet of the compressor, cooling capacity, power consumption, and system EER. The refrigerant temperature at the outlet of the compressor decreases as the bypass rate increases. When the bypass rate is 8.2%, the refrigerant temperature at the outlet of the compressor decreases 2.8℃ while the cooling capacity and EER are the same as the conventional A/C unit. |