Title Experimental Investigation of an Cross-Flow Air-Cooled Plate Heat Exchanger with Single-Wave and Double-Wave Plates
Authors 김민성(Minsung Kim) ; 백영진(Jae-Hoon Lee) ; 박성룡(Seong-Ryong Park) ; 나호상(Ho-Sang Ra) ; 정재훈(Jae Hoon Jeong) ; 임혁(Hyug Lim)
Page pp.347-354
ISSN 1229-6422
Keywords 공랭식 판형열교환기 ; 단일굴곡 ; 이중굴곡 ; 직교류 ; 냉각탑 Air-cooled plate heat exchanger ; Single-wave ; Double-wave ; Cross-flow ; Cooling tower
Abstract Experimental study on a cross-flow air-cooled plate heat exchanger (PHE) was performed. Two types of PHEs were manufactured either with single-wave plates or with double-wave plates in parallel. Cooling air flows through the PHEs in a crosswise direction against internal hot water. The heat exchanger aims to substitute open-loop cooling towers with closed-loop water circulation, which guarantees cleanliness and compactness. In this study, prototype single-wave and double-wave PHEs were designed and tested in a laboratory scale experiments. From the tests, the double-wave PHE shows approximately 50% enhanced heat transfer performance compared to the single-wave PHE. However, the double- wave PHE costs 30% additional pressure drop. For the commercialization, a wide channel design for air flow would be essential for performance and reliability