Title |
The Characteristics of Cooling Performance on 7RT Ammonia Absorption System |
Authors |
이호생(Ho-Saeng Lee) ; 진병주(Byoung-Ju Jin) ; 윤정인(Jung-In Yoon) ; 황준현(Jun-Hyeon Hwang) ; 진심원(Sim-Won Jin) ; 경익수(Ick-Soo Kyung) ; Donald C Erickson(Donald C Erickson) |
Keywords |
냉방성능 ; 암모니아 흡수식 시스템 ; 성능계수 ; 열교환기 Chilling performance ; NH3/H2O absorption system ; COP ; Heat exchanger |
Abstract |
Experimental results for performance characteristics of small NH3 absorption chiller/heater are presented. The apparatus consists of 7RT water-cooled absorption system, solution pump, boiler, cooling tower and peripheral devices. The effect of experimental parameters, such as refrigerant mass flow rate, solution mass flow rate and cooling water temperature have been investigated in view of the system performance. The capacity of each heat exchanger increased as refrigerant mass flow rate increased in cooling mode. Also, a cooling capacity increased as a strong solution mass flow rate increased. The cooling and heating COP show 0.5, 1.5 regardless of refrigerant mass flow rate, respectively. The results focus on the evaluation for performance characteristics of system with respect to variation of refrigerant mass flow rate under standard design conditions. |