Title |
Cooling Performance of Thermoelectric Module with Air-Cooled Heat Exchanger Fins |
Authors |
신재훈(Jae-Hoon Shin) ; 한훈식(Hun Sik Han) ; 김윤호(Yun Ho Kim) ; 김서영(Seo Young Kim) ; 현재민(Jae Min Hyun) |
Keywords |
열저항 ; 열전모듈 ; 성능계수 ; 열교환핀 ; 루버핀 ; 평판핀 Thermal resistance ; Thermoelectric module ; COP ; Heat exchanger fin ; Louver fin ; Plate fin ; |
Abstract |
Thermal performance of louver fin and plate fin in a thermoelectric cooling system with a duct-flow type fan arrangement is analytically evaluated. The thermoelectric cooling system consists of a thermoelectric module and two heat exchanger fins. The analytic results show that the optimized louver fin has lower thermal resistance than plate fin. The COP and heat absorbed rate of the thermoelectric cooling system with optimized louver fins are 10.3% and 5.8% higher than optimized plate fins, respectively. |