Title |
Observation Studies on Field Operation of a Exhausted Heat Recovery System for a 300 kW Class Small Gas Engine Cogeneration System |
Authors |
김민성(Minsung Kim) ; 백영진(Young-Jin Baik) ; 박성룡(Seong-Ryong Park) ; 나호상(Ho-Sang Ra) |
Keywords |
가스엔진 ; 코제너레이션 ; 열병합발전 ; CHP ; 배가스열교환기 ; 배열회수 Gas engine ; Cogeneration ; Combined heat and power ; CHP ; Exhaust gas heat exchanger ; Exhaust heat recovery ; |
Abstract |
An exhausted heat recovery system for a small gas engine cogeneration plant was investigated. The system was designed and built in a 300kW class cogeneration demonstrative system. The basic performance was tested depending on load variation, and installed to a field site as a bottoming heat and power supply system. The exhaust gas heat exchangers (EGHXs) in shell-and-tube type and shell-and-plate type were tested. The entire efficiency of the cogeneration system was estimated between 85 to 90% under the 100% load condition, of which trend appears higher in summer due to the less thermal loss than in winter. Power generation efficiency and thermal efficiency was measured in a range of 31∼33% and 54∼57%, respectively. |