Title Theoretical Review and Experiment on Applicability of Double Skin Facade Ventilated by Fans
Authors 임지혜(Ji Hye Lim) ; 손장열(Jang Yeul Sohn)
Page pp.605-613
ISSN 1229-6422
Keywords 이중외피 ; 팬 ; 환기 ; 실물모형실험 Double skin facade ; Fan ; Ventilation ; Mock-up test
Abstract Double skin facade(DSF) ventilated by fans consists of a normal external and an internal envelope. In this glass layer, the installed fan replaces an air inlet for the control of air flow through the cavity. The purpose of this paper is to investigate physical theory and to analyze the applicability of fans installed in a DSF. The experiment was conducted in 2 rooms. One room has a DSF with installed fans and the other one has a typical window. The room ventilated through a DSF which fans are installed was always kept warmer than the other room, ventilated directly from the outdoors. The average increase of the supplied air temperature through the DSF ventilated by fans was 6.54℃ at 78CMH, 6.2℃ at 95CMH, and 3.7℃ at 120CMH. As a result, the DSF with installed fans was appropriate for installation in rooms. It supplies outdoor fresh air heated through a cavity and ventilates a constant air volume.