Abstract |
In this paper, the appropriate thermal storage time of an air-conditioning system with slab thermal storage was considered by use of summer measurement values. Two standards of heat extraction rate and criterion function were established as the standard that evaluates appropriateness. When heat extraction rate was a standard, zero hour and seven hours were obtained as appropriate thermal storage time, in the case of evaluation by energy consumption and running cost individually. Also, when criterion function was a standard, the difference between energy consumption and running cost was small, it was because the weight function to room air temperature deviation was much bigger than heat extraction rate. |