Title A Study on the Prediction of Indoor Environment in Bio Safety Level 3 Laboratory According to Biohazard Scenario
Authors 박현진(Hyun Jin Park) ; 홍진관(Jin Kwan Hong)
Page pp.745-750
ISSN 1229-6422
Keywords 생물안전 3등급 연구시설 ; 생물재해 시나리오 ; 인플루엔자 A ; 멀티죤시뮬레이션 ; 에너지 소비량 BSL3:Biosafety level 3 lab. ; Biohazard scenario ; Influenza A:H1N1 ; Multizone simulation ; Energy consumption
Abstract Since the implementation of the LMO Law in Korea, the importance of the design qualification of BSL3 lab. is emphasizing. In this study, multizone simulation for three kind of biohazard scenarios using CONTAM is performed for design qualification of BSL3 lab. Also, in the case of unexpected spread of contaminants such as Influenza A virus(H1N1) in BL3 zone, the design qualification is carried out for diffusion and decontamination of contaminants according to differential pressure of BSL3 anteroom and door area of BSL3 lab. Also, in this study, appropriateness of laboratory room differential pressure and air flow rate to maintain pressure difference between laboratory rooms, and energy consumption due to air change rate variation according to door area in BL3 lab. Simulation results show that these approach methods are used as a tool for the design and verification of BL3 lab.