Mobile QR Code QR CODE : Korean Journal of Air-Conditioning and Refrigeration Engineering
Korean Journal of Air-Conditioning and Refrigeration Engineering

Korean Journal of Air-Conditioning and Refrigeration Engineering

ISO Journal TitleKorean J. Air-Cond. Refrig. Eng.
  • Open Access, Monthly
Open Access Monthly
  • ISSN : 1229-6422 (Print)
  • ISSN : 2465-7611 (Online)
Title A Study on Estimating Real-time Thermal Load During GHP Operation in Heating Mode
Authors 서정아(Jeong A Seo) ; 신영기(Younggy Shin) ; 오세제(Se-Je Oh) ; 정상덕(Sang-Duck Jeong) ; 지경철(Kyoung-Chul Ji) ; 정진희(Jin Hee Jeong)
Page pp.32-37
ISSN 1229-6422
Keywords 가스엔진구동 열펌프 ; 고장검출 ; 압축기 ; 자동제어 ; 부하추정 ; R410a GHP ; Fault detection ; Compressor ; Control ; Load estimation ; R410a ;
Abstract The present study has been conducted to propose an algorithm regarding real-time load estimation of a gas engine-driven heat pump. In the study, thermal load of an indoor unit is estimated in terms of air-side and refrigerant-side. The air-side estimation is based on a typical heat exchanger model and is found to be in good agreement with experimental data. When it comes to the refrigerant-side load, a pressure difference across a valve must be estimated. For the estimation, it is assumed to be proportional to a bigger pressure difference that is available either by measurement or by estimation. Relative good agreement between the air- and refrigerant- sides suggests that the assumption may be plausible for the load estimation. The summed flow rate of all of indoor units is in good agreement with the throughput of the compressor which are calculated from the manufacturer’s software. Accordingly, estimated thermal loads are also in good agreement. The proposed algorithm may be further developed for improved control algorithm and fault diagnosis.