Title |
Ventilation Performance According to Outdoor and Operating Conditions of the Vertical Exhaust Duct System in High Riser Public Houses |
Authors |
김영배(Young Bae Kim) ; 김재홍(Jae-Hong Kim) ; 성재용(Jaeyong Sung) ; 이명호(Myeong Ho Lee) |
Keywords |
환기 성능 ; 굴뚝 효과 ; 루프팬 ; 지하 댐퍼 ; 배기입상덕트 Ventilation performance ; Stack effect ; Roof fan ; Basement damper ; Vertical exhaust duct |
Abstract |
The ventilation performance of a vertical exhaust duct system in the high riser public house has been evaluated by a commercial software, Fluid Flow, which solves pressure losses through the duct system including bathroom fans and a hybrid roof fan. During the numerical simulations, outdoor wind condition and stack effects in summer and winter were considered as well as the operating conditions of a basement damper and the roof fan. The results show that the bathroom ventilation in summer is the most unsatisfactory. The opening of the basement damper has a problem that the polluted air in the lower floors is exhausted to the underground parking lot, not to the rooftop. If the basement damper is closed, the exhaust flow rate in the lower floors is not sufficient due to the strong flow resistance in the long vertical duct even though the roof fan is under operating. |