Title |
Experimental Study on Heating Performance Characteristics of Air Source Heat Pump with Air to Water Type |
Authors |
이권재(Kwon Jae Lee) ; 권영철(Young Chul Kwon) ; 전종균(Chong Keun Chun) ; 박삼진(Sam Jin Park) ; 권정태(Jeong Tae Kwon) ; 허철(Cheol Huh) |
Keywords |
공기-물 ; 성능계수 ; 난방능력 ; 히트펌프 ; 성능 Air to water ; COP ; Heating capacity ; Heat pump ; Performance |
Abstract |
This paper presents the heating performance characteristics of the air source heat pump with air to water type. The heating capacity, COP, P-h diagram were measured at various operating conditions, air-side temperatures, relative humidities, and inlet/outlet water temperature under the standard heating condition of KS B 6275. The experimental data for the heat pump were measured using the air-enthalpy calorimeter and the constant temperature water bath. As the air-side temperature increases, the heating capacity and COP increase. The effect of the air-side relative humidities on the heat pump performance is insignificant. The heat pump performance on inlet and outlet water temperatures and air-side temperatures(-7, -11, -15℃) were studied. Heating capacity and COP increased about 27~39% with the air-side temperature increasing. Enthalpy between the front and the rear of condenser decreased about 6% by increasing of the inlet water temperature. These results can be utilized in the design of the air source heat pump system with air to water type. |