Title |
An Experimental Study on the Dehumidification Characteristics and the Effectiveness for Operating Conditions of a Desiccant Rotor |
Authors |
강병하(Byung Ha Kang) ; 이진주(Jin Joo Lee) ; 김석현(Sukhyun Kim) |
DOI |
http://dx.doi.org/10.6110 /KJACR.2012.24.1.029 |
Keywords |
제습로터 ; 제습 ; 제습 유용도 ; 절대습도 Desiccant rotor ; Dehumidification ; Dehumidification effectiveness ; Humidity ratio |
Abstract |
An experimental study has been carried out to investigate the dehumidification characteristics for several operating conditions of a compact desiccant rotor. This problem is of particular interest in the design of a desiccant type of dehumidifier. Room temperature, room humidity, regeneration temperature, revolution speed and frontal air velocity of desiccant rotor are varied as operating conditions. The results obtained indicate that dehumidification rate is increased with an increase in the room humidity while dehumidification effectiveness is not changed much. It is also found that the optimal rotor speed and optimal regeneration temperature exist for maximum dehumidification rate and dehumidification effectiveness. |